ReFlex Power™ Programming Manual AC Module Remote Programming
90 M380056-03 Rev L
Programmable configuration: stand alone, parallel or phase group
R
EADBACK
F
UNCTIONS
Measure voltage, current, frequency, and phase
Voltage, current and frequency settings (phase, if in a phase group)
Soft voltage and current limits
Over/Under Voltage and Over Current protection setting
Status and Accumulated Status registers
Programming error codes
Fault codes
Manufacturer, power supply model, serial number, and firmware
version identification
4.3
POWER-ON CONDITIONS
Table 4-1 presents remote power-on conditions for the AC Power Supply.
Table 4-1. Remote Power-On Conditions
Condition Default
Voltage 0 Volts (initial power–on voltage). Also see CAL<n>:INIT:VOLT
Current 7.140 Amps (initial power–on current). Also see CAL<n>:INIT:CURR
Frequency 60 Hz
OVP Trip Voltage
154 V (110% of Module Maximum Voltage, which is 140 V) +7% (initial power–
on OVP). See CAL<n>:INIT:VOLT:PROT
Output OFF
Parallel No Modules Paralleled
Voltage Range Low
Phase 0.0 degrees, stand alone mode
OCP Trip Current
7.42 A (Maximum current 102% of the full scale current, which is 7 A for low
voltage range)