Chapter 3: Programming
Installation and Maintenance Manual
8
C) will display the total number of setpoints available for use in
the currently selected active program.
D) To display the active program, depress .
To change programs, with the unit in the Program mode, depress
.
NOTE: Program 0 is the first program. If 10 programs were previously selected using Code 770,
there will be programs 0-9.
CIR# 7- 7- -2 ENT-
CIR# - 7-
-
ENT-
-
ENT
7 1
(0 thru Highest Program Number)
3.9: Setpoints
Programming New Setpoints
A) Unit must be in the Program mode.
B) Select a limit switch circuit for programming. Depress .
The circuit number selected cannot exceed the number of output relays specified earlier using
CIR# 177. See Section 3.5: Selecting Number of Outputs.
C) Depress . The will set the selected relay turn-on
point.
D) Depress . . This will set the selected relay turn-off
point.
E) Multiple ON and OFF setpoints can be programmed on each circuit. All decimal points will
flash when more than one setpoint exists on the selected circuit.
F) An LS (Limit Switch) may not have the same value for both the ON point and the OFF point.
If a value is entered that is already a setpoint for that LS, only the new one will be used. For
example: If LS1 had an ON point at 100 and an OFF point of 100 was entered, the ON point
at 100 would be deleted. The OFF point at 100 would then be entered. Assuming that these
were the only setpoints, the output would turn ON at 0 and OFF at 100.
CIR#
-
-
(1 thru 30) -
ENT
CIR OFF
-
(Desired Pos)
ENT
-
CIR ON
-
(Desired Pos)
ENT