Ametek 1995L Micro-Set PLS Manual de usuario Pagina 19

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 33
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 18
15
Installation and Maintenance Manual
Chapter 5: Fault Check
Chapter 5: Fault Check
The Fault Check option provides an automatic in-process self-diagnostic mechanism to verify that all
PLS functions are operating properly.
The Fault Check option will detect and disable system operation in the event of any of the following
problems:
1. Analog to digital converter or associated electronic failure.
2. Microprocessor or 5 volt power supply failure.
Non-system-type faults, such as individual output failures, will not be sensed. It is recommended that
the Fault Check output be used as an operate enable type signal. Loss of this output should immedi-
ately stop the process which is being controlled.
The Fault Check input may be operated by an isolated contact, current sourcing, or current sinking
device 5V DC at 10mA.
A normally closed, momentary open contact button can be wired per Fig 10-1, Fig. 10-2, OR
Fig. 10-3 (Chapter 10: Wiring Diagrams), to activate the Fault Check circuit, and it will provide a
method of resetting the fault output after a fault condition has been sensed.
To reset the Fault Check output after the fault condition has been cleared, the fault reset input must be
deactivated (open circuit) and then re-actuated. Cycling the fault reset input will cycle the fault check
relay to verity that the Fault Check output is operating properly.
NOTE: If the Fault Check inputs are not wired, the display will still show when there is a fault and the
outputs will be disabled, but it will not lock on the fault. However, if the fault check inputs are
wired up per Fig. 10-1, Fig. 10-2 or Fig. 10-3 (Chapter 10: Wiring Diagrams), upon seeing
a fault, the fault check relay will drop out and all outputs will shut off until the fault is fixed and
the fault check input is reset.