4
The type of information contained in each reading varies depending on the probe type. Table 2 species the data
pattern for various probe types.
Table 2 - Reading Data Type Specication by Probe Type
Types 1, 2, 3 Types 4, 5, 6
Reading 1 Temp 1 Temp 1
Reading 2 Product or Water* Product or Water*
Reading 3 Low Ref Temp Temp 2
Reading 4 Product Product
Reading 5 High Ref Temp Temp 3
Reading 6 Product Product
Reading 7 Low Ref Temp Temp 4
Reading 8 Product Product
Reading 9 High Ref Temp Temp 5
Reading 10 Product Product
Reading 11 Circuit Temp Circuit Temp
Reading 12 Product Product
Reading 13 Low Ref Temp Low Ref Temp
Reading 14 Product Product
Reading 15 High Ref Temp High Ref Temp
* For single oat probes, this frame contains product data.
For dual oat probes, this frame contains water data.
When calculating Water or Product positions, one must consider whether or not the probe uses a reference
magnet. For probes that use a reference magnet (type 3 and type 6), position can be calculated using the
following formula:
Position = Measured Period/Wire Speed
Where:
Measured Period = the time between pulses in a reading (ms)
Wire Speed = (ms / inch)
Position = distance from internal reference
For probes that do not use a reference magnet (types 1, 2, 4, and 5), position can be calculated using the
following formula:
Position = Measured Period/Wire Speed*2